YOTAI | YTDL-H27, SF6 Comprehensive Detector

Rp0

Price : INQUIRY
Status : PRE-ORDER
MOQ : 1 PCS
Delivery Time : 3 – 6 Weeks
Delivery Point : Warehouse Jakarta – Indonesia

Stok 100

SKU: I&C/ANZ/YTDL-H27 Kategori: , Tag: , , Brand:

Deskripsi

SF6 Comprehensive Detector

Model : YTDL-H27

MFR : Electric Power Equipment (Shanghai) Co., Ltd

Introduction: The instrument displays the SF6 gas purity curve, dew point, humidity, SO2, H2S, and CO values ​​in real time, and tracks changes in gas humidity. This completes three functional tests simultaneously, significantly conserving gas, effectively protecting the environment and reducing pollution, while also reducing user workload and improving work efficiency. The humidity sensor is from Vaisala, Finland; the purity sensor is from HNP, Germany; and the decomposition product sensor is imported from Alpha, UK, specifically for SF6.

Overview :

SF6 gas micro-water meter

The SF6 comprehensive tester (YTDL-H27) can be used to test the purity, humidity, and decomposition products of SF6 gas in equipment. It can also detect SO2, H2S, and CO components in SF6 gas. The SF6 comprehensive tester uses the TCD method for purity testing, the resistance-capacitance method for humidity testing, and the electrochemical sensor method for decomposition product testing. After SF6 gas measurement begins, the instrument automatically determines equilibrium and displays the SF6 gas purity curve, dew point and humidity values, SO2, H2S, and CO values ​​in real time, while also tracking changes in gas humidity. This simultaneous performance of all three functions significantly conserves gas, effectively protects the environment, reduces pollution, and reduces user workload, improving efficiency. Humidity sensors are from Vaisala, Finland; purity sensors are from HNP, Germany; and decomposition product sensors are imported from Alpha, UK, specifically for SF6. Product alternative names: SF6 comprehensive tester, sulfur hexafluoride comprehensive tester, SF6 moisture tester, SF6 decomposition product analyzer, SF6 comprehensive analyzer, SF6 purity tester.

Technical requirements :

( 1) Purity testing. Technical requirements: The purity measurement value is 90% to 100%, and the error does not exceed 0.05%.

(2) Humidity detection. DL/T506-2007 stipulates that the technical requirements for humidity measurement using the mirror method are as follows: When the ambient temperature is 20°C, the dew point measurement range is 0-60°C, and the measurement error does not exceed ±0.6°C.

(3) Detection of decomposition products.

1) Using the principle of electrochemical sensor, it can simultaneously detect the content of SO2, H2S and CO components of SF6 gas in the equipment.

2) The detection range for SO2 and H2S gases should not be less than 100μL/L, and the detection range for CO gas should not be less than 500μL/L.

3) The gas flow rate required for detection should not exceed 300mL/min, and the response time should not exceed 60s.

4) The detector interface can be connected to the gas valve of the equipment and can withstand the gas pressure inside the equipment.

5) It should be used within the validity period of the inspection report and must be inspected every year.

6) Based on performance indicators, detectors are divided into Class A and Class B. Class A detectors are typically used to determine whether equipment has a potential fault by detecting SF6 gas decomposition products in the equipment. Class B detectors are typically used to detect gas decomposition products after equipment failure. The main performance indicators are the instrument’s accuracy and repeatability.

Features :

  • Fast measurement: no preheating is required after power on, and dew point saturation is quickly reached
  • Portable design: The instrument is lighter, easy to carry and use. 
  • Fast measurement: No need to wait after the instrument is turned on, it can measure immediately and quickly obtain the purity value, trace water value, and the detection value of each decomposition product
  • Fast and gas-saving: The gas consumption during measurement is only about 0.5L (101.2kPa). 
  • Self-locking joint: Self-locking joint imported from Germany, safe, reliable and leak-free.
  • Data storage: large capacity design, can store up to 100 sets of test data.
  • Clear display: The LCD screen directly displays the purity value, time and date, battery power, etc.
  • RS232 interface: can be connected to a serial printer to print data. 
  • Built-in power supply: Built-in large-capacity rechargeable lithium battery, which can work continuously for 10 hours on a full charge.

Technical Parameters :

Micro-water parameters

Parameter Item Parameter Value
Measuring range Dew point -80~+20℃ (supports PPMV, etc.), dew point accuracy: ±0.4℃ (when the dew point temperature is lower than 0℃, the sensor output is frost point)
Dew point accuracy ±0.4℃ (When the dew point temperature is lower than 0℃, the sensor output is frost point)
Response time 63%〔90%+20- -20℃ Td 5s[45s]
Resolution Dew point 0.1℃ or 0.1PPM
Repeatability ±0.4℃, gas flow SF6 is adjusted to 0.5~0.9L/min
Gas flow SF6 is adjusted to 0.5~0.9L/min
Probe protection Stainless steel sintered filter
Measuring range 0~100% SF6; Accuracy and repeatability: ±0.4%, independent of flow rate;
Response time 90%, 15s
Accuracy ±1ppm
Display Mode Large color LCD display
Operating voltage 220VAC±10%50Hz, AC/DC dual-use, overcharge protection, built-in 3500mAH rechargeable battery
Work pressure 0~1.0MPa
Output interface USB 1.1 Specification
Operating Environment Temperature: -20~+60℃

Decomposition parameters :

project index
Minimum detection amount 0.1ppm
stability When the temperature changes from 20℃ to 40℃, the zero point drift is ≤±0.1ppm
Accuracy When measuring ≤2ppm, the error is ≤±0.1ppm
When measuring >2ppm, the error is ≤±0.2ppm
Measuring range SO2+SOF2: 0~100μL/L; (0~2000μL/L)
H2S: 0~100μL/L
HF: 0-20 μL/L
CO: 0-1000 μL/L
Measurement tolerance H2S≤10μL/L,±1μL/L; H2S>10μL/L,±10%

CO≤10μL/L,±0.5μL/L;CO>10μL/L,±1.0μL/L

Resolution SO2+SOF2≤0.1μL/L, H2S≤0.1μL/L,
CO≤0.5μL/L, HF≤0.1μL/L
Response time **Not more than 5 minutes
pressure The instrument pipeline can withstand a pressure of no less than 1MPa
Temperature range -40℃~+50℃
Humidity range ≤95%RH
atmospheric pressure 86kPa~106kPa
Inlet pressure ≤1.0Mpa

Purity parameters :

purity Measuring range 0%~100%
Measurement accuracy ±0.5%
Measurement time <2 minutes.
Ambient temperature    -40℃~+60℃
Ambient humidity    0~100% RH
power supply    AC 220V
   Built-in rechargeable battery

Requirements for measuring moisture content in sulfur hexafluoride circuit breakers

Test content Standard (u1/1, 20°C)
Sulfur hexafluoride circuit breaker leaving the factory and undergoing overhaul (before overall reassembly)

The moisture values ​​of the breaking unit and the supporting unit should be measured separately.

≤150
During handover, measure the moisture content of the circuit breaker from the inflation interface at the bottom of the support. ≤150
During operation, the moisture value of the circuit breaker is measured by the inflation interface at the bottom of the support.

The test cycle shall be in accordance with the “Preliminary Test Procedures”.

≤200
During operation, if necessary (breaking unit leakage, disassembly of breaking unit), the water content of the breaking gas chamber of the sulfur hexafluoride circuit breaker should be measured separately at the self-sealing joint in the junction box. ≤300