Deskripsi
132KV Outdoor High Voltage Disconnecting Switch
Series : GW4
MFR : Lugao Power Co.,Ltd
132KV Outdoor High Voltage Disconnecting Switch.
The GW4 Outdoor Disconnecting Switch is composed of a base, an insulating strut, a conductive part, and an operating mechanism. Each pole is equipped with two pillars, and the upper end of each pillar is fitted with a conductive knife. The contacts of the knife are positioned in the middle of the two pillars. At the lower ends of the pillars, bearing sleeves are installed. Driven by the operating mechanism, the knife can be horizontally rotated by 90° to fulfill the requirements of opening and closing. The outdoor disconnecting switch is designed for use in three-phase AC 50Hz electrical systems to switch on/off the high-voltage circuit when there is no load in the circuit, allowing charging or transferring of the circuit. It is also used to disconnect the current with the bus bar, breaker, or any other high-voltage electrical equipment during circuit maintenance.
Operating Environment :
1. Altitude: no more than 3000m;
2. Ambient air temperature: the upper limit is 40C, the lower limit is -25C;
3. The wind speed does not exceed 35m/s;
4. The earthquake intensity is more than 8 degrees;
5. The contamination level does not exceed Class II;
6. The thickness of ice coating is not more than 10mm;
7. The installation site should be free from flammable and explosive hazards, chemical corrosion and severe vibration.
Specification :
| Type | GW4-40.5 | GW4-72.5 | GW4-126 | GW4-126G | GW4-145 | |
| Rated voltage kV | 40.5 | 72.5 | 126 | 126 | 145 | |
| Rated current A | 630 1250 | 630 1250 | 630 1250 | 630 1250 | 1250 2000 | |
| 2000 2500 | 2000 2500 | 2000 2500 | 2500 | |||
| Short time withstand current ( rms) kA | 20 31.5 | 20 31.5 | 20 31.5 | 20 31.5 | 20 31.5 | |
| 40(46) | 40(46) | 40(46) | 40(46) | |||
| Peak withstand current ( peak ) kA | 50 80 | 50 80 | 50 80 | 50 80 | 50 80 | |
| 100(104) | 100(104) | 100(104) | 100(104) | |||
| Rated short-time power frequence withstand voltage ( rms ) kV | to each | 80 | 140 | 185 | 185 | 275 |
| -230 | ||||||
| between breaks | 110 | 160 | 210 | 210 | 315 | |
| -265 | ||||||
| Lighting impulse withstand voltage ( peak ) kV | to each | 185 | 325 | 450 | 450 | 650 |
| -550 | ||||||
| between breaks | 215 | 375 | 520 | 550 | 750 | |
| -630 | ||||||
| Horzontal force of terminal N | 550 | 735-750 | 1000 | 1000 | 1500 | |
| -750 | ||||||
| Weigh of single pole kg | 80 | 200 | 240 | 300 | 3 | |

Features :








Ulasan