Panel Mount Flame Detector Amplifier
Model : IDD9000
Brand : FORNEY
The IDD 9000 flame amplifier is designed to easily upgrade existing Forney flame amplifiers. Most installations simply replace the flame amplifier and rewire existing wiring to improve flame detection and identification capabilities.
The IDD 9000 is available in panel or rack mount configurations; single or dual channel configurations. The dual channel configuration uses two completely independent channels to support two flame detectors simultaneously.
Compatible Flame Detectors:
- IDD-II, Filtered, Infrared Detector Part #38321-21
- IDD-IIU, Unfiltered, Infrared Detector Part #38321-22
- IDD-IIL, Infrared Detector for Lignite Part #38321-23
- UV-4, UV Tube Detector Part #379189-02
Specifications:
Temperature: 32° to 140°F (0° to 60°C)
Humidity: 5% to 95% relative humidity, non-condensing
Power Requirements: 120/240 VAC, 50/60 Hz @ 12 VA
Output Relay Ratings (SPDT): 3 A at 125 VAC, 250 VAC & 30 VDC
3 relays are available for each channel (Lamp, Main Flame & Alarm).
3 relays are available for each channel (Lamp, Main Flame & Alarm).
Flame Strength: 4-20 mA or 0-10 VDC (sourcing)
Flame Failure Response Time (FFRT): 2.0, 3.0 or 3.8 seconds
Flame Pickup Time: less than 2 seconds
Nonvolatile RAM: 8 complete operating profiles
Approvals: Factory Mutual (FM)